Case History 113, published two months ago,
described the theory behind the Protuner tuning methodology, but
how well does it work in real life?
This article describes just a few cases of the
performance of real loops taken from various plants, and
compares how they performed before with the as-found tuning, and
then afterwards with Protuner analysis and tuning.
The first case which is taken from a large chemical
plant is of a level control which required ‘tight’ control
(i.e. keeping the level as closely as possible at setpoint).
Please note that the recordings shown are not the originals
which are hard to read due to noise and other disturbances, so
they have been "cleaned" by putting them through an
accurate simulation. However they reproduce faithfully what
really did happen in the plant.
Apart from the tuning, no problems were found with
the loop. The tuning parameters settings were:
P = 1.5, and I = 8.0 minutes per repeat.

Fig. 1
Figure 1 shows the closed loop ‘as-found’ test
which was recorded over a 3 hour period. It can be seen how bad
the response was to a 10% step change in setpoint, being
extremely slow and very cyclic. It had still not fully settled
out at the end of the 3 hour period.
The Protuner tuning which was made from an open
loop step change gave the following settings for a fast
response:
P = 12.0 and I = 12.0 minutes per repeat.

Fig.2
The new response is shown in Figure 2. The PV
reached the new setpoint within 8 minutes, and had completely
settled out a short while later.
A second example of how good the tuning is comes
from a plant where I was performing optimisation at the time of
writing this article. This was also a level control which is
extremely important. The flow into the tank is extremely
variable. If the level drops too low, then the large pump that
draws liquid out of the tank starts cavitating, and wears out
quickly. With the existing control, the plant has been replacing
pumps on a monthly, and sometimes even weekly basis, which has
cost them an enormous amount of money!
The original as found tuning was:
P = 3, and I = 600 seconds per repeat.
The Protuner tuning gave:
P = 8, and I = 300 seconds per repeat.

Fig.3
Figure 3 which is taken from a report on the plant’s
Process Plus continuous loop monitoring package shows 3
recordings, of which the top and bottom show the story:
The top one shows the level process variable. The
left hand side is the control with the original tuning. The
level fluctuates all over the place. It is no wonder that the
pump was cavitating. The performance with new tuning is on the
right. The incredible improvement in control can be seen. The
level now stays within a really tight band.
The bottom trace is that of the controller output.
It can be seen on the right side that the valve is working much
harder with the new tuning. This is to be expected. As mentioned
in a recent Case History, all that one does with control is to
transfer the variance from the one side of the process to the
other, and this is what has happened here. Sometimes people say
that you can’t let a valve work like that, and yes, the valve
is going to wear out more quickly, but this is a case where the
valve must be sacrificed for the control. Economically the valve
will still last much longer than the pumps did, and is also much
cheaper. This will save a lot of money over a year
The next example of differences between original
and Protuner tuning, is of a critical and relatively slow
temperature process in a chemical plant. The setpoint of the
controller comes from a higher level advanced control system.
The process is also subject to frequent and fairly fast load
disturbances. Poor performance severely jeopardises product
quality. The operators were very unhappy with the performance of
this important loop

Fig.4
Figure 4 shows responses to setpoint changes with
the as-found tuning. It can be seen that the process takes a
very long time to respond and is jumping around quite badly.
The original as found tuning was:
P = 0.25, I = 0.7 minutes per repeat, and D =
0.2 minutes. A filter of 0.2 minutes was inserted in front
of the process variable.
The Protuner tuning gave:
P = 1.4, and I = 0.7 minutes per repeat.
The D and filter were removed.

Fig.5
The resulting performance was brilliant as shown in
Figure 5 which shows a long term test recorded over 15 hours
with the new Protuner tuning. (Please note that the scale of the
recording is over a very small range of only 5%, so the traces
are magnified considerably). During part of the period the
setpoint coming from the advanced control was changing. The
temperature stayed with ±1.5 ºC in a measurement range of 0 -
225 ºC. As can be seen from the variations going on in the
movements of the controller output, the tuning was coping
brilliantly with load disturbances!
In the previous article, Case History 113, which
described the Protuner’s tuning methodology, it was mentioned
that Techmation does not recommend closed loop tuning for
various reasons, including that it is difficult to get a truly
representative sample of the process dynamics, especially when
any valve problems exist. The next example illustrates this
point perfectly.

Fig. 6
Figure 6 is the recording of a setpoint change made
on a flow loop. The trace on the top (black) is the controller
output. It can be seen that when the setpoint was changed, how
the flow stayed where it was. This was due to the valve
sticking. After a small initial proportional jump, the output
went into a constant ramp which was caused by the integral
trying to get the valve to move. Eventually the valve broke free
and the flow reached setpoint, and shortly after that the valve
jumped further up past setpoint. The controller then started
ramping back down to try and get the flow back down to setpoint.
After it had moved only a few percent the valve suddenly
reversed and jumped back down way below setpoint.
The whole process then repeated a couple more
times, and finally the flow did get to setpoint.
It can be seen from this that any tuning system
that tried to use this response for tuning would be doomed to
failure, as the responses are in no way related to the dynamics
of the process. Admittedly this is a bit of an extreme case, but
when you take into account that at least 50% of control loops
have problems, 80% of them generally due to valve problems, then
you can realise that tuning in automatic has very little chance
of success.
There is no doubt at all in my mind that the only
way to do tuning is to follow all the procedures to ensure that
one does get a step truly representative of the process
dynamics, and this is only generally possible by making step
changes in manual. I also believe that if one is to succeed then
you do also need a proper tuning package like the Protuner,
especially with complex process dynamics.
To site a specific example, in an article recently
published in Intech, the journal of the ISA, one of the world’s
leading control experts stated that it is beyond the capability
of most control practitioners to successfully tune most
temperature loops by trial and error, as it takes too long.
Successful optimisation needs in-depth
understanding of practical control and the analytical and tuning
tools to carry it out.